EEBA - Click for Home
Line

We Welcome Your Comments

Education That Works

Site Map | Search | Home   

EEBA Criteria

The Energy and Environmental Building Association (EEBA) has developed these goals, objectives and criteria for energy and resource efficient buildings. They provide guidance for design, construction and comprehensive rehabilitation (gut-rehab) of low-rise residential and small commercial buildings less than 20,000 square feet (1,900 m2) floor area.


Goals for Energy and Resource Efficient Building

Energy Efficiency

To promote building practices that result in a substantial reduction in energy use for space conditioning, water heating, lighting and appliance operation.

Improved energy efficiency can reduce the environmental impact of the built environment, improve economic well being and promote global stability.

Occupant Safety

To promote building practices that result in an improvement in fire and structural safety.

Improved construction practices can reduce the risk from earthquakes, hurricanes, floods and fires.

Occupant Health

To promote building practices that result in an improvement in the indoor environment.

Improved construction practices can reduce the risk from building related illness and sick building syndrome.

Durability

To promote building practices that prolong the useful service life of buildings, reduce maintenance and promote serviceability.

Rehabilitation and replacement of damaged components and structures results in the inefficient use of resources. Improper moisture control can lead to premature failure of building components and can contribute to poor environmental conditions for occupants.

Occupant Comfort

To promote building practices that improve thermal comfort, daylighting, lighting, humidity control, odor control, noise control and vibration control.

Providing comfort for building occupants is one of the fundamental requirements of shelter.

Environmental Impact

To promote building practices that reduce the impact on the local and global environment.

The impacts of the built environment on the planetary environment make it necessary to make informed, environmentally responsible choices during the construction process.


Objectives for Energy and Resource Efficient Building

Energy Efficiency

Energy efficient and resource efficient construction should address the following objectives for design, construction, commissioning, operation and maintenance.

A. Building Structure

Thermal transmission through heat loss and heat gains should be reduced by the specification and installation, with proper attention to detail and quality assurance, of increased levels of thermal insulation. Insulation systems should be installed such that they reduce convective, conductive and radiative heat losses and gains. Thermal anomalies such as thermal bridges should be minimized.

Moisture gain resulting in decreased thermal and structural performance should be controlled. Air flow retarder systems and vapor diffusion retarders should be used to protect the building envelope from uncontrolled air and moisture flow.

Thermal transmission through convective heat loss and gain driven by "wind-washing" should be reduced by the specification and installation, with proper attention to detail and quality assurance, of an external air barrier system or external "weather barrier."

Fenestration systems should be selected according to climate, building orientation, interior comfort, daylighting, ventilation, furnishing durability and egress requirements.

B. Mechanical Systems

Indoor air quality should be facilitated by the installation of a controlled mechanical ventilation system. Heat recovery is recommended in severe heating climate zones.

Only sealed combustion or power vented direct combustion appliances should be installed in occupied spaces. Gas cook tops and gas ovens should only be installed in conjunction with exhaust fans.

Thermal and peak load reductions derived from improving levels of insulation, airtightness and fenestration performance of the building envelope should be evaluated in the sizing of equipment.

The domestic hot water system should meet high efficiency standards. Options for reducing water consumption are recommended. Solar energy for hot water heating should be considered.

Efficient illumination design and lighting systems should be used. Natural lighting of spaces should be considered prior to specifying electric illumination systems. Lighting designs and controls should consider the availability of natural light. Occupancy sensors should be considered for foyers, utility room, basements, garages and other spaces. Hard wired general area lighting should employ fluorescent fixtures. Other lighting fixtures should use compact fluorescent lamps.

Major appliances should meet high energy efficiency standards using current appliance ratings.

C. Occupant Considerations

A comprehensive operations manual should be provided to occupants which includes necessary operating, maintenance and repair information so that the performance of the building can be maximized.

Occupant Safety

In no case should the application of energy efficient or resource efficient design or construction strategies, materials, equipment or appliances violate safety codes and standards.

A. Building Structure

Recognized structural design shall be employed to resist live, static and wind loads.

B. Mechanical Systems

Mechanical systems shall be designed and constructed to facilitate occupant safety.

C. Occupant Considerations

Information relating to the safe operation of the building and mechanical systems shall be provided to occupants. Information relating to safe maintenance of installed mechanical systems shall also be provided.

Occupant Health

Energy efficient and resource efficient construction should provide a healthy living and working environment.

A. Building Structure

Selection of construction materials that have low emission rates of toxic materials; foundations designed to exclude entry of soil gas; and implementation of moisture control measures are recommended.

B. Mechanical Systems

A controlled mechanical ventilation system should be provided to facilitate occupant health.

C. Occupant Considerations

Information relating to the healthy operation of the building and its mechanical systems should be provided to the occupants.

Durability

Energy efficient and resource efficient construction should include the following moisture control measures in order to provide long term performance and durability.

A. Building Structure

The building envelope should provide mechanisms to control the migration of moisture in the liquid and vapor form.

Building materials and components should be protected from rain, snow and other moisture sources during storage on site, construction and commissioning of the building.

B. Mechanical Systems

Controlled ventilation, mechanical cooling or dehumidification systems should be provided to maintain acceptable indoor relative humidity. Such systems and their controls should maintain humidity in the range of 25 to 60 percent. Source control of moisture should be used where possible.

C. Occupant Considerations

Instructions for the proper use and maintenance of moisture control systems should be provided to occupants.

Occupant Comfort

Energy efficient and resource efficient construction should provide a comfortable living and working environment.

A. Building Structure

The building envelope should facilitate the comfort of occupants.

B. Mechanical Systems

The mechanical systems should facilitate the comfort of occupants.

C. Occupant Considerations

Information relating to the comfortable operation of the building and its mechanical systems should be provided to the occupants.

Environmental Impact

Energy efficient and resource efficient construction should minimize the impact on the environment. Design and construction strategies which account for full life-cycle energy consumption and resource utilization—including the reuse, recycling and reconfiguration of materials and practices—should be used.

A. Building Structure

The building envelope should be deployed on its site and in its local environment in an environmentally sensitive fashion.

Use of virgin materials or materials with low recycled content should be minimized.

On-site reuse of surplus construction materials should be provided. Recycling of materials should be maximized.

B. Mechanical Systems

The energy efficiency of mechanical conditioning systems should be maximized.

C. Occupant Considerations

Information relating to the resource efficient operation and performance of the building should be provided to the occupants. Measures facilitating the recycling of consumer waste should be utilized.


Criteria for Energy and Resource Efficient Building

The following criteria are recommended for the design and construction of energy and resource efficient buildings.

Component Criteria

A. Building Structure

Overall energy consumption for heating, cooling and water heating should meet Energy Star requirements (30% improvement over a standard reference home based on the envelope and equipment requirements of the 1993 Model Energy Code) as determined by an accredited home energy rating system procedure.

Air leakage of buildings (determined by pressurization testing) should be less than 2.5 square inches/100 square feet leakage ratio (CGSB, calculated at a 10 Pa pressure differential); or, 1.25 square inches/100 square feet leakage ratio (ASTM, calculated at a 4 Pa pressure differential); or, 0.25 cfm/square foot of building envelope surface area @ 50 Pa.

B. Mechanical Systems

Controlled mechanical ventilation at a minimum base rate of 20 cfm per master bedroom and 10 cfm for each additional bedroom will be provided when the building is occupied.

A capability to increase the base rate ventilation on an intermittent basis to 0.05 cfm per square foot of conditioned areas will also be provided.

Intermittent spot ventilation of 100 cfm will be provided for each kitchen. Intermittent spot ventilation of 50 cfm or continuous ventilation of 20 cfm when the building is occupied will be provided for each washroom/bathroom.

Positive indication of shut-down or improper system operation for the base rate ventilation will be provided to occupants.

Mechanical ventilation shall use less than 0.5 watt/cfm for ventilation systems without heat recovery or less than 1.0 watt/cfm for ventilation systems with heat recovery.

Mechanical ventilation system airflow should be tested during commissioning of the building.

Heat recovery on controlled mechanical ventilation is recommended in severe heating climate zones. Heat recovery rates of heat recovery ventilators should be greater than 65 percent, including effectiveness of distribution.

Total ductwork leakage for ducts distributing conditioned air should be limited to 10.0 percent of the total air handling system rated air flow at high speed determined by pressurization testing at 25 Pa.

Ductwork leakage to the exterior for ducts distributing conditioned air should be limited to 5.0 percent of the total air handling system rated air flow at high speed determined by pressurization testing at 25 Pa.

Only sealed combustion or power vented direct combustion appliances should be installed in occupied spaces. These appliances must be rated to vent properly at largest expected negative pressure. Gas cooktops and gas ovens should only be installed in conjunction with exhaust fans.

Major appliances should meet high energy efficiency standards using current appliance ratings. Select only those appliances in the top one-third of the DOE Energy Guide rating scale.

Lighting power density should not exceed 1.0 Watts per square foot.

C. Occupant Considerations

Systems that provide control over space conditioning, hot water or lighting energy use should be clearly marked. Information relating to the operation and maintenance of such systems should be provided to occupants.

The designer and general contractor should provide comprehensive information to occupants relating to the safe, healthy, comfortable operation of the building and mechanical systems.

Indoor Environment Criteria

Energy efficient and resource efficient construction should provide comfortable indoor conditions as defined by ASHRAE Standard 55-1989 (Addendum 55a-1994).

A. Building Structure

The building and site should provide effective drainage measures to control rainfall runoff and to prevent entry into the building.

The building foundation should be designed and constructed to prevent the entry of moisture and other soil gases.

Building assemblies should be designed and constructed to permit drying of interstitial spaces.

Building assemblies should be designed and constructed to prevent airflow into insulation systems from both the interior and exterior.

Radon resistant construction practices as referenced in the ASTM Standard E-1465-90 "Radon Resistant Design and Construction of New Low Rise Residential Buildings" should be utilized.

Materials, adhesives and finishes with tested low emission rates should be selected.

B. Mechanical Systems

Controlled mechanical ventilation systems shall be installed.

Where combustion appliances are used, only sealed direct combustion or power vented systems should be installed in habitable spaces. Gas cooktops and gas ovens should only be installed in conjunction with exhaust fans.

Forced air systems should be designed to provide balanced airflow to all conditioned spaces and zones. Interzonal air pressure differences should be limited to 3 Pa.

Filtration systems should be provided for forced air systems which provide a minimum atmospheric dust spot efficiency of 30 percent (derived from ASHRAE Standard 52.1-1992).

Indoor humidity should be maintained in the range of 25 to 60 percent by controlled mechanical ventilation, mechanical cooling or dehumidification.

C. Occupant Considerations

Occupants should be provided with an operator’s manual containing specific operating instructions on how to maintain a healthy indoor environment.

Control systems should include advisory display or indicative modes to alert occupants to "trouble" or "failure" conditions.

Environmental Impact Criteria

Energy efficient and resource efficient construction should be designed, constructed and operated to reduce overall life-cycle impact on the environment considering energy consumption, resource use and labor inputs in the fabrication, erection, modernization, operation and disassembly of the building, components and systems.

The design and construction of buildings should use recycled materials, or new materials with a high recycled content. Minimization of scrap on site and design for disassembly should be provided.


Discussion Relating to Criteria

The Criteria are for the most part self-explanatory. However, two concepts require explanation: air leakage coefficients and ductwork leakage. The following discussion relates to these two concepts.

In selecting the approach to measure/evaluate energy use the following factors were considered:

  • A single airtightness value was selected as it has become clear that it is as important to build a tight building envelope in the hot, humid south as in the cold north. Similarly, mixed, humid climates and hot, dry climates also require tight building envelopes. The importance of tight construction goes far beyond energy conservation. Health and durability are the principle concerns with respect to this issue.
     
  • The airtightness value is based on the surface area of the building envelope not the volume. Air change per hour at 50 Pascals was rejected as a basis for measurement because it confuses the issue. We are dealing with leakage through the building envelope. Holes, holes, holes. Of course, ach @ 50 Pa is a popular, albeit misguided, criteria. The requirements have been translated for information purposes only. Based on ach @ 50 Pa, values are between 3.2 and 2.8 for 1,500 to 2,500 square foot houses with basements (not including the basements in these square footage determinations). The airtightness value is roughly double the Canadian R-2000 tightness requirement of 1.5 ach @ 50 Pa although it is roughly twice as tight as conventional construction.

Air Leakage -- Determining Leakage Ratios and Coefficients

Using a blower door, measure the flow rate necessary to depressurize the building 50 Pascals. This flow rate is defined as CFM50. Alternatively, determine the Equivalent Leakage Area (EqLA) in square inches at 10 Pascals using the procedure outlined by the Canadian General Standards Board (or alternatively, determine the ELA using the ASTM procedure calculated at 4 Pascals). When determining these values, intentional openings (design openings) should be closed or blocked. These openings include fireplace dampers and fireplace glass doors, dryer vents, bathroom fans, exhaust fans, HRV’s, wood stove flues, water heat flues, furnace flues and combustion air openings.

Calculate the leakage ratio or the leakage coefficient using the entire surface area of the building envelope. When determining the surface area of the building envelope, below grade surface areas such a basement perimeter walls and basement floor slabs are included.

For example, a 2,550 square foot house constructed in Grayslake, IL has a building envelope surface area of 6,732 square feet and a conditioned space volume of 33,750 cubic feet (including the basement). The measured Equivalent Leakage Area (EqLA) using a blower door is 128 square inches. This also corresponds to a blower door measured CFM50 value of 1,320 cfm and a blower door measured 2.3 airchanges per hour at 50 Pascals.

Surface Area EqLA CFM50 ach @ 50 Pa Volume
6,723 ft2 128in2 1,320 cfm 2.3 33,750 ft3

To determine the Leakage Ratio, divide the surface area of the building envelope by 100 square feet and take this interim value and divide it into the EqLA.

6,732 ft2 » 100 ft2 = 67.32

128 in2 » 67.32 = 1.9 in2/100 ft2
(Leakage Ratio)

To determine the Leakage Coefficient, divide the CFM50 value by the surface area of the building envelope.

1,320 CFM50 » 6,732 ft2 = 0.20 cfm/ft2
(Leakage Coefficient)

Many airtightness measurements are recorded as air changes per hour at a pressure differential of 50 Pascals (ach @ 50 Pa). To convert ach @ 50 Pa to CFM50 multiply the volume of the building envelope (including the basement) by the ach @ 50 Pa and divide by 60 min/hour.

For example, 2.3 ach @ 50 Pa across a building envelope of volume 33,750 ft3 is equivalent to a CFM50 value of 1,320 cfm.

33,750 ft3 x 2.3 ach @ 50 Pa » 60 min/hr = 1,320 CFM50

Ductwork Leakage

To determine the allowable limit for ductwork leakage, determine the rated air flow rate of the air handler, furnace, air conditioner, etc. at high speed from the manufacturer’s literature. For example, a typical heat pump system may have a high speed flow rate of 1,200 cfm across the blower according to literature supplied with the unit. Ten percent of this value is 120 cfm. This 10 percent value becomes the total ductwork leakage limit when the total air handling system is depressurized to 25 Pascals with a pressurization test of the distribution system.

Privacy Policy Web Link Policy Contact Us

Inside EEBA | Houses That Work | Conference & Expo | Bookstore | Institute | Legacy Campaign
Resources | Partners / Alliances | Events Calendar | Media | Related Sites | Get Involved | Site Map | Search | Home

© 2008 Energy and Environmental Building Association
6520 Edenvale Boulevard, Suite 112, Eden Prairie, MN 55346
952.881.1098  fax: 952.881.3048  inquiry@eeba.org